Acoustic sylomer laboratory test

NEW LABORATORY TEST RESULTS FOR THE AKUSTIK + SYLOMER MOUNTS IN DOWEL-LAMINATED TIMBER (DLT) STRUCTURES

3/2/2022

INTRODUCTION

Dowel-Laminated Timber (DLT) structures are similar to Nail-Laminated Timber (NLT) structures but without the need for nails or metal fasteners. Dowel-Laminated panels are an all-wood structure and can be easily processed using CNC machinery, allowing on site modifications.

Different tests have been carried out using different solutions for the floating floor from a naked structure to an installation with several cement board layers with our floating mounts.

THE PRODUCTS THAT HAVE BEEN TESTED ARE:

AKUSTIK + SYLOMER FLOOR MOUNTS

The Akustik + Sylomer® Floor mounts are vibration isolators that have been designed for the installation of wooden floors with a batten system. Their easy installation and low space requirement allows exceptional vibration and noise isolation as part of a floating floor application.

These mounts are typically installed every 19,69''. But this feature may be tuned in order to adapt to the load or natural frequency requirement of the application. The natural frequency at their optimal loading point reaches values below 12 Hz. These technical properties provide a high level of noise and vibration isolation when used in light wooden structures.

RESULTS OF THE LABORATORY TESTS

In order to show the acoustic advantages when using Akustik+Sylomer® Floor mounts in a Dowel-Laminated Timber structure, an independent external technological centre has performed impact noise tests using different building configurations.

Based on the obtained test results, an impact noise reduction up to 26dB can be obtained, compared to the reference configuration, without any Akustik+Sylomer® Floor mount

The tested configurations are shown below as well as different comparisons between different configuration systems:

System A1

Scheme Impact noise results - calculated according to Standard ASTM E1007
A1 System A1
Description
  • DLT floor 5,94'' (5,51'' DLT +0,43'' OSB)
Go to the Impact Noise Results Report (PDF)

System A2

Scheme Impact noise results - calculated according to Standard ASTM E1007
light_slab_22mm System A2
Description
  • DLT floor 5,94'' (5,51'' DLT +0,43'' OSB)
  • 1,97'' wooden battens
  • Akustik + Sylomer® floor mount 25
  • 0,32'' OSB
Go to the Impact Noise Results Report (PDF)

System A3

Scheme Impact noise results - calculated according to Standard ASTM E1007
A3 System A3
Description
  • DLT floor 5,94'' (5,51'' DLT +0,43'' OSB)
  • 1,97'' wooden battens
  • Akustik + Sylomer® floor mount 25
  • 3,50'' Rockwool insulation
  • 0,32'' OSB
Go to the Impact Noise Results Report (PDF)

System A4

Scheme Impact noise results - calculated according to Standard ASTM E1007
A4 System A4
Description
  • DLT floor 5,94'' (5,51'' DLT +0,43'' OSB)
  • 1,97'' wooden battens
  • Akustik + Sylomer® floor mount 25
  • 3,50'' Rockwool insulation
  • 1 layer cement board
Go to the Impact Noise Results Report (PDF)

System A5

Scheme Impact noise results - calculated according to Standard ASTM E1007
A5 System A5
Description
  • DLT floor 5,94'' (5,51'' DLT +0,43'' OSB)
  • 1,97'' wooden battens
  • Akustik + Sylomer® floor mount 25
  • 3,50'' Rockwool insulation
  • 2 layer cement board
Go to the Impact Noise Results Report (PDF)

System A6

Scheme Impact noise results - calculated according to Standard ASTM E1007
A6 System A6
Description
  • DLT floor 5,94'' (5,51'' DLT +0,43'' OSB)
  • 1,97'' wooden battens
  • Akustik + Sylomer® floor mount 25
  • 3,50'' Rockwool insulation
  • 3 layer cement board
Go to the Impact Noise Results Report (PDF)

System A7

Scheme Impact noise results - calculated according to Standard ASTM E1007
A7 System A7
Description
  • DLT floor 5,94'' (5,51'' DLT +0,43'' OSB)
  • 1,97'' wooden battens
  • Akustik + Sylomer® floor mount 25
  • 2 layer cement board
  • 0,43'' laminated floor
Go to the Impact Noise Results Report (PDF)

System A8

Scheme Impact noise results - calculated according to Standard ASTM E1007
A8 System A8
Description
  • DLT floor 5,94'' (5,51'' DLT +0,43'' OSB)
  • 1,97'' wooden battens
  • Akustik + Sylomer® floor mount 25
  • 3,50'' Rockwool insulation
  • 1,50'', normal strength concrete topping
Go to the Impact Noise Results Report (PDF)

OVERVIEW

Influence of the Rockwool installation Impact noise results - calculated according to Standard ASTM E1007 Comparation between different layers of the Cement Board Impact noise results - calculated according to Standard ASTM E1007
Influence Rockwool Comparation Cementboard
Influence of the laminated floor Impact noise results - calculated according to Standard ASTM E1007 Comparation between the Cement Board layers and the Concrete Topping Impact noise results - calculated according to Standard ASTM E1007
Influence Laminated floor Comparation Cementboard
Overview Impact noise results - calculated according to Standard ASTM E1007
Overview Impact noise results